GCK, GCS, MNS Low-Voltage Withdrawable Switchgear2025-11-29

Operating Environment for GCK, GCS, and MNS Low-Voltage Withdrawable Switchgear Assemblies
3.1 The ambient air temperature shall not exceed 40℃, and the average temperature measured over a 24-hour period shall not exceed 35℃. The minimum ambient air temperature is -5℃;
3.2 The altitude of the installation site shall not exceed 2000m;
3.3 The ambient air shall not be significantly polluted by dust, smoke, corrosive or combustible gases, vapors, or salt spray;
3.4 Atmospheric conditions:
The air shall be clean. At a temperature of +40℃, the relative humidity shall not exceed 50%. Higher relative humidity is permitted at lower temperatures.
For example, the relative humidity may reach 90% at +20℃. However, moderate condensation that may occasionally occur due to temperature changes shall be taken into consideration;
3.5 When installed, the inclination of the equipment from the vertical plane shall not exceed 5°;
3.6 The equipment shall be installed in locations free from severe vibration and impact;
Note: If users have special requirements, please consult our company for further arrangements.
Technical Parameters
Rated Main Circuit Voltage (V)
AC380(400), (600)
Rated Auxiliary Circuit Voltage (V)
AC110, 220(230), 380(400)
DC110, 220
Rated Frequency (Hz) 50(60)
Rated Insulation Voltage (V) AC660(1000)
Rated Current (A)
Horizontal Busbar 1000, 1250, 1600, 2000, 2500, 3150, 4000
Vertical Busbar (MCC) 630, 800
Rated Short-Time Withstand Current of Busbar (kA·s) 30, 50, 80
Rated Peak Withstand Current of Busbar (kA/0.1s) 63, 105, 176
Power-Frequency Withstand Test Voltage (V·min)
Main Circuit 2500
Auxiliary Circuit 1800
Handle 3750
Degree of Protection
IP30, IP40